PVC Insulation Power Cable_VV、VLV、VY、VLY、Z-VV、Z-VLV、VV22、VLV22

PVC Insulation Power Cable

  • 电力电缆.jpg

1.     Application:

The transmission and distribution lines with the rated voltage of 0.6/1kV and below.

Cable conductor allows the maximum continuous operation temperature of 70℃ and 160℃ of short-circuit with 5 seconds.

2.     Type & Model:

                            Type

                        Model

Cooper conductor

Aluminum conductor

VV

VLV

PVC Insulted & PVC Sheath Power Cable

VY

VLY

PVC Insulted & PE Sheath Power Cable

Z-VV

Z-VLV

Flame Retardant PVC Insulted & PVC Sheath Power Cable

VV22

VLV22

PVC Insulted & Steel-tape Armoring PE Sheath Power Cable

Z-VV22

Z-VLV22

Flame Retardant PVC Insulted & Steel-tape Armoring PE Sheath Power   Cable

VV23

VLV23

PVC Insulted & Steel-tape Armoring PE Sheath Power Cable

Remarks:  Flame Retardant includes three classes of A/B/C, so it’s necessary to mark this point when placing an order, for example: ZA-VV、ZB-VV、ZC-VV.

3.     Production Range;

                Type

                                Nominal Conductor Cross Section (mm2)

Single core

2 cores

3 cores

3+1cores

4 croes

5cores

4+1 cores

3+2 cores

Copper core

VV

1.5~1000

1.5~185

1.5~300

4~300

4~240

1.5~185

4~185

4~185

VY

1.5~1000

1.5~185

1.5~300

4~300

4~240

1.5~185

4~185

4~185

VV22

10~1000

4~185

4~300

4~300

4~240

4~185

4~185

4~185

VV23

10~1000

4~185

4~300

4~300

4~240

4~185

4~185

4~185

Aluminum core

VLV

2.5~1000

2.5~185

2.5~300

4~300

4~240

2.5~185

4~185

4~185

VLY

2.5~1000

2.5~185

2.5~300

4~300

4~240

2.5~185

4~185

4~185

VLV22

10~1000

4~185

4~300

4~300

4~240

4~185

4~185

4~185

VLV23

10~1000

4~185

4~300

4~300

4~240

4~185

4~185

4~185

4.  Performance

  1). Finished cables can pass the test of 3.5kV/5min.

  2). Maximum DC conductor resistances at 20℃ for finished cables are as following:

Nominal Cross Section

(mm2)

Copper Conductor

(Ω/km)

Aluminum Conductor

(Ω/km)

Nominal Cross Section

(mm2)

Copper Conductor

(Ω/km)

Aluminum Conductor

(Ω/km)

Nominal Cross Section

(mm2)

Copper Conductor

(Ω/km)

Aluminum Conductor

(Ω/km)

1.5

12.1

-

25

0.727

1.20

150

0.124

0.206

2.5

9.41

-

35

0.524

0.868

185

0.0991

0.164

4

7.61

7.41

50

0.387

0.641

240

0.0754

0.125

6

3.08

4.61

70

0.268

0.443

300

0.0601

0.100

10

1.83

3.08

95

0.193

0.320

400

0.0470

0.0778

16

1.15

1.91

120

0.153

0.253

500

0.0366

0.0605

5. Cable Laying Suggestion:

  1). Both cable & environment temperatures should be above 0℃ and keep thus for 24 hours.

  2). Minimum Allowed Bending Radius should be not less than

  Single core cable:20(D+d)

  Multi-core cable:15(D+d)

  remarks:D-outer cable diamter

  d-conductor diameter

  If the conductor is not circle:d=1.13√s

  (“s”is the standard section) 

Product name:   PVC Insulation Power Cable

Model:   VV、VLV、VY、VLY、Z-VV、Z-VLV、VV22、VLV22、Z-VV22、Z-VLV22、VV23、VLV23

Rated voltage:   0.6/1kV

AL/PVC/PVC/SWA/PVC 0.6/1kV Multicore core armored cable
AL/PVC/PVC/AWA/PVC 0.6/1kV Single core armored cable
AL/PVC/PVC 0.6/1kV Multicore unarmored cable
AL/PVC/PVC 0.6/1kV Single core unarmored cable
CU/PVC/PVC/SWA/PVC 0.6/1kV Multicore armored cable
CU/PVC/PVC/AWA/PVC 0.6/1kV Single core armored cable
CU/PVC/PVC 0.6/1kV Multicore unarmored cable